NFPA 72 - 2013
|
NFPA 1221 - 2016
|
NFPA 1221 - 2019
|
In-Building Solution Required
|
NFPA 1 Section 11.10
|
NFPA 1 Section 11.10
|
NFPA 1 Section 11.10
|
Pathway Survivability for Coaxial Cable Required
|
2 Hour for Riser Coaxial Cable – Sec. 24.3.6.8
|
2-Hour for Riser Coaxial Cable - Sec. 9.6.2.1.3
|
Backbone Cable Routed Through Enclosure Matching Bldgs. Fire Rating Sec. 9.6.2.3
|
Plenum Rated Coaxial Cable Required
|
Yes, Riser & Feeder Coaxial Cable Sec. 24.3.6.8
|
Yes, Riser & Feeder Coaxial Cable – Sec. 9.6.2.1.1.1
|
Yes, Backbone & Antenna Distribution Cables Sec. 9.6.2.1
|
Lightning Protection Required
|
Not addressed in Section 24.5.2
|
Yes, In accordance with NFPA 780 – Sec. 9.6.3
|
Yes, Section 9.6.3 Installed per NFPA 780
|
Isolation of Donor Antenna Required
|
Yes, 15 db – Sec. 24.5.2.3.3
|
Yes, 20 db – Sec. 9.6.9
|
Yes, 20 dB Above System Gain Sec. 9.6.9
|
Battery Backup Required
|
12 Hours – Sec. 24.5.2.5.5.2
|
12 Hours – Sec. 9.6.12.2
|
12 Hours Battery or Generator Section 9.6.12.2
|
Signal Strength & Area Coverage Required
|
-95 dBm – Sec. 24.5.2.3
90% General – Sec. 24.5.2.2.2
99% Critical – Sec. 24.5.2.2.1
|
DAQ 3.0 - Sec. 9.6.8
90% General - Sec. 9.6.7.5
99% Critical - Sec. 9.6.7.4
|
DAQ 3.0 - Sec. 9.6.8
90% General - Sec. 9.6.7.4
99% Critical - Sec. 9.6.7.3
|
Monitoring By Fire Alarm Required
|
Yes – Sec. 24.5.2.6
|
Yes – Sec. 9.6.13
|
Yes – Sec. 9.6.13 & Chapter 10 of NFPA 72
|
Cabinets for Equipment & Battery Backup Required
|
Yes, NEMA 4/NEMA 4X –
Sec. 24.5.2.5.2
|
Yes, NEMA 4/NEMA 4X – Sec. 9.6.11.2
|
Yes, NEMA 4/4X & NEMA 3R for Batteries Sec. 9.6.11.2
|
Monitor Antenna Malfunction Required
|
Yes, Donor Antenna – Sec. 24.5.2.6(2)(a)
|
Yes, Donor Antenna – Sec. 9.6.13.1(2)(a)
|
Yes, Donor Antenna – Sec. 9.6.13.2.1(5)
|
System Acceptance/Testing
|
Section 24.5.2.1.2 &14.4.10
|
Section 9.6.4, 11.3.9 & 11.3.9.1
|
Section 9.6.4, 11.3.9 & 11.3.9.1
|
Listing of Equipment
|
Not Specifically Addressed
|
Not Specifically Addressed
|
Specific Listing Requirement TBD by the AHJ
|
 |
IFC - 2015
|
IFC - 2018
|
IFC - 2021
|
In-Building Solution Required
|
Sec. 510.1
|
Sec. 510.1
|
Sec. 510.1
|
Pathway Survivability for Coaxial Cable Required
|
Not Specifically Addressed in Section 510. Referenced in 2013 NFPA 72 Sec. 24.3.6.8
|
Yes, Section 510.4.2. Reference to NFPA 1221. ** Also See NFPA 1221 TIA 16-2
|
Yes, Section 510.4.2. Reference to NFPA 1221.
|
Plenum Rated Coaxial Cable Required
|
Not Specifically Addressed in Section 510. Referenced in 2013 NFPA 72 Sec. 24.3.6.8
|
Yes, Sec. 510.4.2. Reference to NFPA 1221
|
Yes, Section 510.4.2
Reference to NFPA 1221
|
Lightning Protection Required
|
Not Specifically Addressed in Section 510
|
Yes, Sec. 510.4.2 Per NFPA 780 as Referenced in NFPA 1221
|
Yes, Sec. 510.4.2 Per NFPA 1221 Sec. 9.6.3 Installed per NFPA 780
|
Isolation of Donor Antenna Required
|
Not Specifically Addressed in Section 510
|
Yes, 20 db – Sec. 510.4.2.4 (4)
|
Yes, 20 db – Sec. 510.4.2.4 (4)
|
Battery Backup Required
|
24 Hours – Sec. 510.4.2.3
|
12 Hours – Sec. 510.4.2.3 or 2- Hours Battery w/ Emergency Generator
|
12 Hours – Sec. 510.4.2.3 or 2- Hours Battery w/ Emergency Generator
|
Signal Strength & Area Coverage Required
|
-95 dBm – Sec. 510.4.1
95% General – Sec. 510.4.1
99% Critical – Not Specifically Addressed in Sec. 510
|
DAQ 3.0 - Sec. 510.4.1.1
95% General - Sec. 510.4.1
99% Critical - Sec. 510.4.2 Reference to NFPA 1221
|
DAQ 3.0 - Sec. 510.4.1.1
95% General - Sec. 510.4.1
99% Critical - Sec. 510.4.1
|
Monitoring By Fire Alarm Required
|
Not Specifically Addressed in Sec. 510 – See 2013 NFPA 72
|
Yes – Sec. 510.4.2.5
|
Yes – Sec. 510.4.2.5
|
Cabinets for Equipment & Battery Backup Required
|
Yes, NEMA 4 – Sec. 510.4.2.4 (1) & (2)
|
Yes, NEMA 4/NEMA 3R – Sec. 510.4.2.4 (1) & (2)
|
Yes, NEMA 4/NEMA 3R – Sec. 510.4.2.4 (1) & (2)
|
Monitor Antenna Malfunction Required
|
Not Specifically Addressed in Section 510
|
Yes, Donor Antenna – Sec. 510.4.2.4(4)
|
Yes, Donor Antenna – Sec. 510.4.2.4(4)
|
System Acceptance/Testing
|
Section 510.5.3
|
Section 510.5.3
|
New – Section 510.5.4
Annual – Section 510.6.1
|
Listing of Equipment
|
Not Required by Section 510
|
Not Required by Section 510
|
Yes, Section 510.4
|
Mounting of Donor Antenna
|
Not Specifically Addressed
|
Not Specifically Addressed
|
Section 510.5.1
|